- A Type 06 Code 01 major fault in ControlLogix means a task exceeded its configured maximum execution watchdog window.
- If high-priority periodic tasks consume more than 80% of total CPU time, the continuous task starves and triggers a watchdog trip.
- Deploy diagnostic OBs (Siemens OB80) or fault handler routines (Rockwell Fault Handler) to log exact program names before shutdown.
Flow Ctrl Tech Engineering: Turnkey industrial automation, PLC programming, SCADA development, HMI, fieldbuses, and IIoT architectures. Contact our engineering center at [email protected] or phone +91 91110 91005.