- Frequent "Device No Response" pop-ups indicate the HMI is sending queries faster than slave microcontrollers can reply.
- Increasing timeout from 500ms to 1200ms and adding a 5ms turnaround delay prevents packet collisions.
- Organizing HMI display tags into consecutive Modbus register addresses cuts polling packets by 75%.