- The original Modbus specification only defines 16-bit registers; 32-bit float encoding is manufacturer-dependent.
- The four primary permutations are ABCD (Big Endian), CDAB (Word Swap / Mid-Little Endian), BADC (Byte Swap), and DCBA (True Little Endian).
- Always test numerical scaling by reading known static calibration registers (such as frequency setpoint or manufacturer model ID).