- Filters are triggered to backwash by differential head loss, runtime timer (typically 48 to 72 hours), or turbidity breakthrough.
- Air scour must precede water backwash to rub media grains against each other and detach sticky biological floc.
- Freshly backwashed media requires a "Filter-to-Waste" ripening period to rebuild the micro-straining surface mat before feeding drinking water mains.
Flow Ctrl Tech Engineering: Turnkey industrial automation, PLC programming, SCADA development, HMI, fieldbuses, and IIoT architectures. Contact our engineering center at [email protected] or phone +91 91110 91005.